Skip to main content
Skip table of contents

Sensor Alarms

Each sensor has an alarm setpoint: an acceptable range, including a high and low threshold and an alarm delay period.

Depending on the sensor, this may be a temperature range, a humidity range, a CO2 range, etc.

For example, a temperature sensor in a blood transfusion fridge may be configured to trigger an alarm if it exceeds 6°C or falls below 1°C for more than 10 minutes (see image 1).

A sensor alarm is triggered if a sensor goes out of range for longer than its delay period.

High Temperature Alarm.PNG

Image 1: A high temperature alarm

If a unit exceeds its high threshold/falls below its low threshold, the supplies inside may be at risk unless prompt action is taken.

If a sensor is in isolation when it goes out of range, an alarm will not be triggered.

If the sensor is still out of range after the isolation ends, an alarm will appear on the WARP display panel, but not on the CAM+ Website, nor will contacts be notified.

After you resolve the issue, it may take some time for the temperature, humidity, CO2, etc. to come back in range. Once it is back in range, it may take up to 5 minutes for the WARP to send data to the cloud and readings to update on the CAM+ Website.

Your account may be configured to trigger an alarm to inform you that the unit has come back in range. If so, the alarm will end with '(Cleared)’, for example, 'High Temperature Alarm (Cleared)'.

See Alarm Settings Report for instructions on how to view all alarm setpoints of all sensors in a department.

See Modify an Alarm Setpoint for instructions on how to edit a sensor's high/low alarm threshold and alarm delay period.

Types of Sensor Alarms

Alarm

Description

High Temperature

A high temperature alarm is triggered if a sensor exceeds its high temperature threshold for longer than its alarm delay period.

Low Temperature

A low temperature alarm is triggered if a sensor falls below its low temperature threshold for longer than its alarm delay period.

High Humidity

A high humidity alarm is triggered if a sensor exceeds its high humidity threshold for longer than its alarm delay period.

Low Humidity

A low humidity alarm is triggered if a sensor falls below its low humidity threshold for longer than its alarm delay period.

High Pressure

A high pressure alarm is triggered if a sensor exceeds its high pressure threshold threshold for longer than its alarm delay period.

Low Pressure

A low pressure alarm is triggered if a sensor falls below its low pressure threshold threshold for longer than its alarm delay period.

High O2

A high O2 alarm is triggered if a sensor exceeds its high O2 threshold for longer than its alarm delay period.

Low O2

A low O2 alarm is triggered if a sensor falls below its low O2 threshold for longer than its alarm delay period.

High CO2

A high CO2 alarm is triggered if a sensor exceeds its high CO2 threshold for longer than its alarm delay period.

Low CO2

A low CO2 alarm is triggered if a sensor falls below its low CO2 threshold for longer than its alarm delay period.

High Liquid Level

A high liquid level alarm is triggered if a sensor detects that the contents of a liquid container has exceeded its high threshold for longer than its alarm delay period.

Low Liquid Level

A low liquid level alarm is triggered if a sensor detects that the contents of a liquid container has fallen below its low threshold for longer than its alarm delay period.

Tripped

A tripped alarm is triggered if a Dual Alarm/Status Contact Sensor is tripped.

Depending on what the sensor is monitoring, this could indicate various events.

For example, an alarm triggered by a sensor on a refrigerator door may indicate that the door has been left open.

In other instances, a Dual Alarm/Status Contact Sensor may be connected to a non-Checkit sensor, such as a temperature or CO2 sensor built into the unit. In such cases, a tripped alarm may indicate that the sensor has exceeded/fallen below its high/low temperature or CO2 threshold.

The sensor description (which appear in System field of the alarm notification) should help you determine what has caused the tripped alarm, for example, Blood Plasma Refrigeration Unit Door Sensor, Vaccine Refrigeration Unit Temperature Sensor, Cell Culture Refrigeration Unit CO2 Sensor, etc.

Sensor Alarm Status

Pending Sensor Alarms

As soon as a sensor goes out of range:

  • A pending alarm will be added to the WARP display panel (see image 2)

  • An alarm delay countdown will be shown on the WARP display panel (see image 3)

If the sensor comes back in range before the delay period ends, the pending alarm will be removed from the WARP display panel.

Active Alarms.png

Image 2: Pending alarms

Alarm countdown.JPG

Image 3: Alarm countdown

Active Sensor Alarms

If the sensor does not come back in range before the delay period ends:

  • Relevant contacts will receive an alarm

  • An active alarm/alert will be added to the WARP display panel (see image 4)

  • The sensor will be displayed in red on the WARP display panel (see image 5)

  • The audible sounder (see image 6) will notify those in the vicinity (if you use this device)

  • You will be required to complete an incident audit recording what you have done to resolve the issue

To view alarm/alert details on the WAPR display panel (see image 7), press the centre membrane button on the WARP twice.

To silence the audible sounder, press the centre membrane button on the WARP once.

Active Alert.png

Image 4: Active Alerts

Alert WARP.PNG

Image 5: Sensor on WARP display panel

image-20240419-155707.png

Image 6: Audible sounder

Table view.JPG

Image 7: Alarm/alert details

JavaScript errors detected

Please note, these errors can depend on your browser setup.

If this problem persists, please contact our support.